This series devices are designed for AC withstand voltage test of substation primary equipment under 550KV or below, mainly composed of variable-frequency power supply, exciting transformer, reactor and capacitive Voltage divider
Features:
1. rated voltage:
27kV--- meets AC withstand voltage test of 10kV cable
working frequency 30-300Hz
Test voltage is not more than 22kV, test time is 5min;
54kV--- meets AC withstand voltage test of 35kV cable
Working frequency 30-300Hz
Test voltage is not more than 52kV, the test time is 60min;
81kV--- meets AC withstand voltage test of 10kV cable
working frequency 30-300Hz
Test voltage is not more than 22kV, test time is 5min;
54kV--- meets AC withstand voltage test of 10kV substation
Working frequency 30-300Hz
Test voltage is not more than 28kV, test time is 1 min;
108kV--- meets AC withstand voltage test of 35kV sbustation
Working frequency 30-300Hz
Test voltage is not more than 100kV test time is 1 min;
2. output voltage waveform distortion rate: <1.0%
3. allow continuous working hours: one time working for 60 minutes
under rated conditions;
4. Quality factor of the device: Q > 30 (f=45Hz)
5. device output waveform: sine wave
6. input power supply: three phase 380V
7. frequency regulation range: 30Hz ~ 300Hz
8. system measurement precision: 1.5%
9. over voltage, over current, zero start and other protection
functions.
COMPOSITION
1. Frequency conversion power supply
(1) rated power: 7 kW
(2) Input voltage: three phase 380V 50Hz
(3) output voltage: 0 ~ 400V adjustable
(4) Output voltage frequency: 30 ~ 300Hz
(5) 0.1Hz regulation step
(6) Frequency instability is less than 0.02%
(7) Output current: 0 ~ 18.75A
2. High voltage reactor (4 units)
(1) rated working voltage: 27kV
(2) rated working current: 1.25A
(3) rated inductance: 100H
(4) Continuous working time: 60min
(5) Temperature rise: less than 65ºc
(6) Working frequency: 30~300Hz
3. excitation transformer
(1) rated capacity: 7.5kVA
(2) input voltage: 400V
(3) output voltage: 1.5/3/6kV
(4) output current: 5/2.5/1.25A
4. capacitance divider (1 units)
(1) self capacitance: 800pF
(2) rated voltage: 110kV
(3) working frequency: 30 ~ 300Hz
(4) uncertainty: 1.5%
(5) Rated voltage: 110kV/800pF
5. test line (1 sets)
Configuration Test object | Reactor 4 sections 33.75kVA/27kV | Excitation transformer output terminal | Test voltage(kV) |
10kV/300mm²/3km | 4 sections in series | 1.5kV | ≤22kV |
35kV/300mm²Cable 1km | Two in series two in Parallel | 3kV | ≤52kV |
35kV/100MW Power Transformer | three in series | 6kV | ≤68kV |
10kV substation | two in series | 1.5KV | ≤28kV |
35kV substation | four in series | 6kV | ≤100kV |
![]() |